变压器额定容量 高压额定电压 低压额定电 高压额定电流 低压额定电 (kVA) (kV) 压(kv) 流(A) 接线组别 (A) 各座 S930/10 30 10 0.4 1.73 43. 3 Dyn11/Yyn0 S1030/10 S1130/10 2.89 S9-50/10 50 10 0.4 72.17 Dyn11/Yyno S1050/10 S1150/10 S9-63/10 9 10 0.4 3.64 90.94 Dyn11/Yyno S10-63/10 S11-63/10 S980/10 80 0.4 4.62 115. 47 Dyn11/Yyn0 S10-80/10 S1180/10 5.77 S9100/10 100 10 0.4 144.34 Dyn11/Yyn0 S10-100/10 S11-100/10 7.22 S9-125/10 125 10 0.4 180. 43 Dyn11/Yyno S10-125/10 S11125/10 S9160/10 160 10 0.4 9.24 230.95 Dyn11/Yyn0 S10-160/10 S11160/10 S9200/10 200 10 0.4 11.55 288.68 Dyn11/Yyn0 S10-200/10 S11200/10 360. 85 Dyn11/Yyno S9250/10 250 10 0.4 14. 43 S10-250/10 S11250/10 S9315/10 315 10 0.4 18.19 454.68 Dyn11/Yyn0 S10-315/10 S11315/10 S9400/10 400 10 0.4 23.09 577.37 Dyn11/Yyn0 S10400/10 S11400/10 S9-500/10 500 10 0.4 28.87 721. 71 Dyn11/Yyn0 S10500/10 S11500/10 S9630/10 630 10 0.4 36.37 909.35 Dyn11/Yyno S10-630/10 S11-630/10 S9800/10 800 10 0.4 46.19 1154.73 Dyn11/Yyn0 S10800/10 S11800/10 S91000/10 1000 10 0.4 57. 74 1443. 42 Dyn11/Yyn0 S10-1000/10 S111000/10 S91250/10 1250 10 0.4 72.17 1804. 27 Dyn11/Yyn0 S10-1250/10 S111250/10 1600 S91600/10 10 0.4 92. 38 2309.47 Dyn11/Yyn0S10-1600/10
S111600/10 变压器额定容量 高压额定电压 低压额定电 高压额定电流 低压额定电 (kVA) (kV) 压(kV) (A) 流(A) 接线组别 各座 30 10 0.4 1.73 43. 3 Dyn11/Yyn0 01/056835 SCB10-30/10 50 10 0.4 2.89 72.17 Dyn11/Yyn0 SCB960/10 SCB1060/10 80 10 0.4 4.62 115. 47 Dyn11/Yyn0 SCB980/10 SCB1080/10 100 10 0.4 5.77 144.34 Dyn11/Yyn0 SCB9100/10 SCB10100/10 125 10 0.4 7.22 180. 43 Dyn11/Yyn0 SCB10-125/10 SCB9125/10 160 10 0.4 9.24 230.95 Dyn11/Yyn0 SCB9160/10 SCB10-160/10 00 10 0.4 11.55 288.68 Dyn11/Yyn0 SCB9200/10 SCB10200/10 250 10 0.4 14.43 360. 85 Dyn11/Yyno SCB9250/10 SCB10250/10 315 10 0.4 18.19 454.68 Dyn11/Yyn0 SCB9315/10 SCB10315/10 400 10 0.4 23.09 577.37 Dyn11/Yyno SCB9400/10 SCB10400/10 500 10 0.4 28. 87 721.71 Dyn11/Yyn0 SCB9500/10 SCB10500/10 630 10 0.4 36.37 909.35 Dyn11/Yyn0 SCB9630/10 SCB10630/10 008 10 0.4 46.19 1154.73 Dyn11/Yyn0 SCB9800/10 SCB10800/10 1000 10 0.4 57.74 1443. 42 Dyn11/Yyn0 SCB9-1000/10 SCB101000/10 1250 10 0.4 72. 17 1804. 27 Dyn11/Yyn0 SCB10-1250/10 SCB91250/10 1600 10 0.4 92. 38 2309. 47 Dyn11/Yyn0 SCB91600/10 SCB101600/10 00 10 0.4 115. 48 2886.84 Dyn11/Yyn0 SCB92000/10 SCB102000/10 2500 10 0.4 144. 35 3608. 55 Dyn11/Yyn0 SCB92500/10 SCB102500/10
油浸式配电变压器 空载损耗(T) 上方为Dvml1型号: 负载损耗(斜杠 空载电流(A) 短路阻抗(%) 接地电阻(2) 电压比 卡方为Yyn0) 130 110 1. 00 630/600 1²10 10000/400 100 170 150 1. 44 08/016 1²10 10000/400 130 200 180 1.73 1090/1040 1²10 10000/400 150 250 200 2.19 1310/1250 1²10 10000/400 180 290 230 2.60 1580/1500 14 10000/400 200 340 270 3.07 1890/1800 1°4 10000/400 240 400 310 3.70 2310/2200 1°4 10000/400 280 480 380 4.33 2730/2600 14 10000/400 340 560 460 5.05 3200/3050 14 10000/400 400 670 540 6.37 0995/0585 1°4 10000/400 480 800 650 7.51 4520/4300 1°4 10000/400 570 950 780 8 66 5410/5150 14 10000/400 680 1200 920 10.00 6200 4.5 14 10000/400 810 1400 1120 11.55 7500 4.5 1°4 10000/400 980 1700 1320 14.43 10300 4.5 1°4 10000/400 1150 1950 1560 16.24 12000 4.5 14 10000/400 1360 2400 1880 18.48 14500 4.5 1°4 10000/400
1640 干式配电变压器 空载损耗() 空载电流(A) 负载损耗(T) 短路阻抗(%) 接地电阻(2) 电压比 205 1.00 780 180 740 4 110 10000/400 285 1.44 1120 250 1060 4 110 10000/400 380 1. 96 1550 330 1470 4 110 10000/400 410 2.45 1800 360 1690 1°4 10000/400 470 2.71 2100 4 1²4 420 1980 10000/400 550 3.46 2450 490 2320 4 1°4 10000/400 650 3.75 2850 580 2690 4 1°4 10000/400 740 4.69 3250 660 3070 1°4 10000/400 880 5.00 3900 780 3690 1°4 10000/400 1000 6.35 4600 890 4350 4 1°4 10000/400 1180 7.94 5470 1040 5160 4 1°4 10000/400 1350 8.18 6500 1200 6140 6 1°4 10000/400 1540 10.39 7800 1370 7380 6 14 10000/400 1750 12.99 9250 1560 8730 6 1°4 10000/400 2030 16.24 11000 1810 10390 6 1°4 10000/400 2700 20. 79 13500 2400 12770 6 1°4 10000/400 3000 20.21 16200 2700 15300 6 1°4 10000/400 3500 25.26 19500 3150 18420 6 1°4 10000/400
空载容量(kVA) 相数 30 三相 50 三相 63 三相 80 三相 100 三相 125 三相 160 三相 200 三相 250 三相 315 三相 400 三相 500 三相 630 三相 800 三相 1000 三相 1250 三相 1600 三相